Dometic FreshJet Series 4, FreshJet Series 7EN
Interval Inspection/maintenance
Regulary Check whether the condensation water drainage channels (1) at the sides of the roof air condi-
tioner are clear and the condensation water is able to escape.
1
1
Regulary
Clean the filter of the air discharge unit.
2
1
1
2
1. Insert a flat screwdriver or knife into the handle (1) to pull the filters (2) slightly out.
2. Remove the filters by hand.
3. Clean the filters with a detergent solution and let them dry.
4.
Slide the dry filters back in.Fig. on page19
Have the heat exchanger of the roof air conditioner serviced by specialist company.
Once per year
Check the seals between the roof air conditioner and the vehicle roof for cracks and other
damage.
Check whether the fastening bolts are tightened to the correct torque (2.5 Nm
± 0.3 Nm) and adjust if necessary.
12 Troubleshooting
Problem Possible cause Suggested remedy
Not cooling well The roof air conditioner is not set to
cooling.
Set the roof air conditioner to cooling.
19