Installation4.5
1. The refrigerator must be level both directions.
2. There should be 20mm clearance to the wall.
3. Ventilation must be provided as shown in
alternatives A, B, C or D.
4. The ventilation duct must at least measure
105mm x the wid
th of the refrigerator.
5. Only the entire cooling unit must project into
the duct as shown.
6 Air p
assing through the duct must not be
preheated by any source of heat.
7. Ventilation grills, if used, must have openings
of at least 200cm² each.
Please follow the installation details below
carefully. Guarantee is valid for products
installed as described only.
IMPORTANT:
200 cm²
20 mm
The mains plug/socket must be freely accessible once the
miniBar has been installed.