Explains the need for high and low pressure safety switches to prevent explosions.
Provides detailed steps for connecting refrigerant pipes, including pre-charge discharge and leak testing.
Explains connecting power supply, equipotential wire, and sensor wires to the connection box.
Covers connecting the motor thermistor protection to the electronic control module.
Recommends installing an oil differential pressure switch or sensor for oil pump equipped compressors.
Warns against starting the compressor under high vacuum conditions and advises checking oil levels.
Outlines steps for isolating the compressor from the electrical supply before intervention.
Instructs on calling service centers, handling refrigerant leaks, and fire safety measures.
Lists potential causes for the compressor failing to start, like power issues or electrical faults.
Identifies reasons for periodic start/stop, such as valve issues or condenser problems.
Explains causes for decreased performance, including refrigerant load or valve leaks.
Discusses factors leading to low suction pressure, like defrost cycle issues or expansion valve calibration.
Details issues related to low oil pressure or level, such as worn bearings or blocked filters.
Addresses causes for protection trips, including high/low suction pressure or motor defects.