EasyManua.ls Logo

Dover OPW SiteSentinel iSite - Hydrocarbon Liquid Sump Sensor

Dover OPW SiteSentinel iSite
146 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 132 of 145
www.opwglobal.com
Hydrocarbon Liquid Sump Sensor
Part #30-3219-12
The Hydrocarbon Liquid Sump Sensor is designed to detect the
presence of liquid hydrocarbons in sumps, dispenser pans and other
locations where the presence of a hydrocarbon liquid could indicate
that a leak has occurred.
The Hydrocarbon Liquid Sump Sensor contains a carbon-polymer
material that changes its resistance when exposed to liquid
hydrocarbons. In the event of a break in the cable, the system will
activate the alarm.
Hydrocarbon Liquid Sump Sensor
Hydrocarbon Liquid Sump Sensor
Substance Detected:
Liquid Hydrocarbon
Operating Temperature:
-4°F to 122°F (-20°C to +50°C)
Dimensions:
1.7” x 31.2” (4.4 cm x 33.5 cm)
Required Cable:
12’ (3.6 m) gas-and-oil resistant cable
Maximum Wiring Length:
1000’ (305 m)
Nominal resistance
(uncontaminated):
1K - 5K ohms
Nominal resistance
(contaminated):
30K - 200K ohms
Multi-Drop Restriction:
1 per channel
Connections:
Red = Power, Black = Signal
*Maximum Wiring Length is the maximum length of cable to be used
to connect all sensors on an individual channel. The length includes
run of cable from VSmart to each sensor board in the string.

Table of Contents

Related product manuals