Dual-Float Dispenser Sump Sensor
Part No. 30-0232-D-10
This Dual-Float Sensor is the same as a Discriminating Dispenser Pan
Sensor, Part No. 30-0232-DH-10, but without Belcor
®
inside the
sensor. This makes it non-discriminating.
Maximum Wiring Length is the maximum length of cable to be used
to connect all sensors on an individual channel. This length includes
run of cable from VSmart to each sensor board in the string.
Without Belcor
®
inside sensor
Figure 5-15 Dual-Float Dispenser Sump Sensor
Dual-Float Dispenser Sump Sensor Specifications
Primary Use(s):
Dispenser Pan/Sump
Alternate Use(s):
STP Sumps
Detects:
Low Liquid, High Liquid, Fuel
Operating Temperature:
-40°F to 158°F (-40°C to +70°C)
Dimensions:
Length: 11.1” (28.2 cm), Diameter: 2.3” (5.8 cm)
Float Requirements:
Low: 1.5” (3.8 cm), High: 8” (20.3 cm)
Cable Requirements:
Belden #88760 or Alpha #55371
Maximum Wiring Length*:
1,000’ (305 m) field wiring
Multi-Drop Restriction:
16 per I.S. barrier channel (64 per barrier)
Connections:
Red = Power, Black = Signal, Shield = Ground