11.1.1 Installing the 30-3206
NOTE: Hydrocarbons (i.e., gasoline, diesel and jet fuel, etc.) float on water = if this sensor is fully submerged,
the polymer will NOT detect hydrocarbon liquid.
• This sensor requires two (2) Controller Interface Module Positions.
• Review the installation illustration below. Use the supplied cable gland and silicone wire nuts.
• Install seal-offs at both ends of the conduit run.