EasyManua.ls Logo

Dover OPW SiteSentinel iTouch M1500 - Installing the 30-3206

Dover OPW SiteSentinel iTouch M1500
127 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Doc. No.: M1500, Rev. 6
Page 40 of 127
67733 Gross Point Road 900 Santa Fe Dr.
11.1.1 Installing the 30-3206
NOTE: Hydrocarbons (i.e., gasoline, diesel and jet fuel, etc.) float on water = if this sensor is fully submerged,
the polymer will NOT detect hydrocarbon liquid.
This sensor requires two (2) Controller Interface Module Positions.
Review the installation illustration below. Use the supplied cable gland and silicone wire nuts.
Install seal-offs at both ends of the conduit run.
Interstitial Hydrocarbon Liquid/Water Sensor Wiring
I.S. Interface Module Position 1 Terminals
Sensor Wire
+12
Red
Black (hydrocarbon)
No connection
I.S. Interface Module Position 2 Terminals
Sensor Wire
+12
No connection
White (water)
No connection
Figure 11-2 Interstitial Hydrocarbon Liquid/Water Sensor Installation