3.2.4 DTC Installation
3.2.4.1 DTC Remote Enclosure Installation
1. Install the enclosure on a wall with four (4) fasteners (not supplied). The enclosure must be no further
than 50' (15.24 m) from the FSC3000 controller.
2. Install 1/2” or 3/4” rigid steel conduit for the DTC Power Supply.
3. Pull three (3) 14-AWG wires from the breaker panel. Pull Petro-Net
™
wires.
4. Install 1/2” or 3/4” rigid steel conduit for pump communication and pull wires from each dispenser.
NOTE: For more than four (4) pump loops use the manufacturer’s distribution box. Pump
communication conduit is not required if the manufacturer's distribution box is located near the
remote DPC enclosure.
5. Connect Line, Neutral and Ground wires from the breaker panel to the power-connection block.
6. Connect Petro-Net wires to the Petro-Net block.
IMPORTANT: Maintain polarity throughout all Petro-Net connections in your system.
7. Connect pump communication:
l For Wayne CAT installation: Each applicable pump loop on CN5/6/7/8 (refer to Physical Configuration
for correct connections for different installations).
M1700 FSC3000 Installation Manual | Dover Fueling Solutions 66