EasyManuals Logo
Home>D+H>Control Panel>RZN 4503-T

D+H RZN 4503-T Troubleshooting Guide

D+H RZN 4503-T
2 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
D+H UK
D+H UK (DH Mechatronic UK Ltd), Unit 10, Lawnhurst Trading Estate, Cheadle Heath, Stockport, Cheshire SK3 0SD Page 1 of 2
www.dh-partner.co.uk | +44 (0)161 491 4840 | Registered in England 02670985 | VAT No. 611329279 V3
RZN 4503-T Troubleshooting Guide
L AZN- E b
RM
K-T
RT
ZA S
RT 45
Breakglass
2 8 3 1 6 4 7
10kΩ
3 2
LT
SD-O 371
Smoke detector
LT 84-U
Wall Switch
10kΩ
5
COM
10kΩ
1k Ω
Fire alarm
interface
Normally
open, volt
free contact.
-R
OR
10kΩ resistor - orange band
(from RM “R” & “-” in panel).
1kΩ resistor -
red band (from
keyring bag).
10kΩ resistor - orange band
(from RT “T” & “-” in panel).
EM 47 K
Orange
Black
Black
Vent
24v D+H
Mechatronic
drive.
Orange
(High Speed)
White
Brown
End of line terminal resistor
(from MOT E, a & b in panel).
Connection point
(local to vent - by
others)
Display fault indications
Battery fault:
Incorrect connection of the battery.
Earth fault:
Issue with incoming power supply 230 v earth.
Detector Line fault - Solid:
Indicates an issue between the control panel and control elements (re alarm interface, smoke detector or
breakglass).
Each control element requires a single 10kΩ end of line resistor. See above detail.
If no re alarm interface or smoke detector in system, leave 10kΩ end of line resistor in RM terminals “R” & “-”.
If no RT 45 breakglass, leave 10kΩ resistor in RT terminals “T” & “-”.
Detector Line fault - Flashing:
Indicates line deactivated, press the 1/0 Reset button at top of panel to reactivate.
Drive Group fault:
Issue between the control panel and the drive(s). Ensure EM 47 K end of line terminal resistor is connected as
shown above.
Check 2.5 Amp fuse has not blown.
Terminate all
other coloured
cables in
connection
point.
a
MOT
RZN 4503-T / RT 45 breakglass display indications
+ +
Solid green - System healthy, no faults.
+ +
Solid green + ashing yellow - System healthy, no fault. Inbuilt
service timer expired. Contact our service department.
+ +
Flashing yellow - System fault. See panel indications below.
+ +
Solid green + solid red - System healthy + in re.
+ +
Flashing yellow + solid red - System in fault + re.
Alarm open Reset close

Other manuals for D+H RZN 4503-T