EasyManua.ls Logo

DSC PC5020 Power864 - Page 63

DSC PC5020 Power864
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
57
B.4 Battery Lead and AC Power Routing for UL Listed Remote Fire Monitoring Systems with the
PS5350 AC Output Connection
B.5 Sensor Reset for 2-Wire Smoke Detectors
AUX Connection
For fire installations,
lines come through
conduit connections
PC5020CF
5700
KEYBUS
Conduit opening
for battery connection
to PS5350
AC IN Only
Non-Power
Limited access
(Power Limited)
Power Limited
Access
Power Limited
Access
POWER LIMITED
BLACK (-) BATTERY LEAD 12V, 1.5A
RED (+) BATTERY LEAD 12V, 1.5A
NC
AC
16VAC
80 VA
Non-Power
Limited
Connect to any
COM terminal
AC OUT 16VAC, Supervised
to PC5020 AC
To any PC5020 COM terminal
non-supervised
PS5350
External Battery
Charger
AC
IN
AC
OUT
COM
BAT
-
BAT
+
Voltage
Barrier
Voltage
Barrier
Opening
NOTE: The connection between PS5350 and PC5020
for commercial fire, must not be greater than 20ft of
conduit and must be in the same room.
NOTE: All circuits are Power Limited
except AC and battery leads.
Voltage Barrier
80
VA
IMPORTANT: A minimum of 1/4" (6.4mm) separation must
be maintained at all points between power limited wiring
and all other non-power limited wiring and connections.
Wire entry for power limited wiring must be separate from
non-power limited wiring.
IMPORTANT: A minimum of 1/4" (6.4mm) separation must
be maintained at all points between battery/primary AC
wiring and all other wiring and connections.
2-WIRE SMOKE DETECTORS
AUX YEL GRNBLKRED
+
2200
END-OF-LINE
RESISTOR
EOLR-3
(+)
(-)
+ BELL - 1 PGM 2
Compatiblity Identifier: PC5-2
Maximum Operating Voltage: 13.75VDC
Maximum Circuit Resistance: 100
(total)
mix different models on the
same circuit as correct operation
may be impaired.
Do not
Refer to the 2-wire smoke detector compatibility chart in this manual
NOTE: Do not combine the 2-wire smoke detector and 4-
wire smoke detector on PGM2 (only 2-wire smoke detec-
tors on PGM2). Please see section 2.6 section 7.6 ‘Four-Wire
Smoke Detector Zones‘