Eastron SDM220Modbus User Manual
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web: www.eastron.com.cn Email: sales@eastron.com.cn
Default ID is 001
Range: 001~247
Press the “Enter” button, the first digit
flash.
Press the “Scroll” button to change the
value. After choose the new address value,
the user need pressing the “Enter” button
to confirm the setting.
Default value: 9600bps
Range: 1200, 2400, 4800, 9600bps.
Press the “Enter” button, the red digit flash.
Press the “Scroll” button to change the
value.
After choose the new baud rate, the user
need pressing the “Enter” button to
confirm the setting.
Default: None
Option:None, Even, Odd
Press the “Enter” button, the red part flash.
Press the “Scroll” button to change the
option.
After choose the new Parity, the user need
pressing the “Enter” button to confirm the
setting.
Default: kWh
Option:kWh / KVarh / Imp. Kwh /
Exp. kWh / Imp. kVarh / Exp. kVarh