SDM630MCT M-bus Series User Manual 2025 V1.00
2025 EASTRON ELECTRONIC. When electricity matter www.eastrongroup.com
8
Installation
Step 1: Select a 35mm-wide DIN rail, Pull down the back-end clip on the meter to unlock the mounting
mechanism.
Step 2: Align Upper Slot with DIN Rail. Position the upper slot of the meters DIN rail groove onto the DIN rail,
ensuring full contact (see Figure 1).
Step 3: Following the direction indicated in Figure 1, engage the lower slot of the DIN rail groove onto the DIN rail
until audibly seated (see Figure 2).
Step 4: Push up the back-end clip to lock the meter firmly onto the DIN rail (see Figure 3).
Terminal
①~⑳
Measurement Connection
Screw Connection
Diameter
3
.0mm*PH
1
Strip Length
6-7mm
Screw
M3
Rigid/Supple
0.5-2.5mm² (30 ~ 14AWG)
Tightening Torque
0.2Nm
Model
PZ0