SDM630MCT-ML User Manual V1.2
Minimum value of L3 to L1 voltage
For CH02, CH03 and CH04 registers,
CH02 registers is CH01 + 3000;
CH03 registers is CH01 + 6000;
CH04 registers is CH01 +9000.
For example, the registers of V1 of CH01 , CH02, CH03, CH04 are below:
CH01: 30001 ; CH02: 33001; CH03: 36001; CH04: 39001
The addresses below are for the total measurement for all loads:
Modbus
Protocol
Start
Address
Hex
Total import active energy
Total export active energy
Total import reactive energy
Total export reactive energy
Total reactive Energy (3)
Net Total Reactive Energy
Note:
(1). The power factor value indicates the direction of the current. Positive value refers to forward current, negative
value refers to reverse current.
For example, PF=0.98, it means the current is forward flow;
if PF= -0.98, it means the current is reverse flow.
(2). The power sum demand calculation is based on total power = import power – export power.
(3). Total Energy = Import energy + Export energy. For example: total active energy = import active energy + export
active energy
(4). Net Energy = Import energy – Export energy. For example: Net active energy = import active energy – export
active erergy
4.2.2 Holding Register, Function code (Hex): 03(read) / 10(write)
Modbus
Protocol
Start Address
Hex
Read minutes into first demand calculation. When the
Demand Time reaches the Demand Period then the
demand values are valid.
Length : 4 byte
Data Format : Float