SDM630MCT-ML User Manual V1.2
- 20 -
32739
Minimum value of L3 to L1 voltage
4
Float
V
0A
B2
For CH02, CH03 and CH04 registers,
CH02 registers is CH01 + 3000;
CH03 registers is CH01 + 6000;
CH04 registers is CH01 +9000.
For example, the registers of V1 of CH01 , CH02, CH03, CH04 are below:
CH01: 30001 ; CH02: 33001; CH03: 36001; CH04: 39001
The addresses below are for the total measurement for all loads:
Address
(Register)
Input Register Parameter
Modbus
Protocol
Start
Address
Hex
Description
Length
(bytes)
Data
Format
Units
Hi
Byte
Lo
Byte
312049
Sum of line currents.
4
Float
A
2F
10
312053
Total system power.
4
Float
W
2F
14
312057
Total system volt amps.
4
Float
VA
2F
18
312061
Total system VAr.
4
Float
VAr
2F
1C
312073
Total import active energy
4
Float
kWh
2F
28
312075
Total export active energy
4
Float
kWH
2F
2A
312077
Total import reactive energy
4
Float
kVArh
2F
2C
312079
Total export reactive energy
4
Float
kVArh
2F
2E
312081
Total apparent energy
4
Float
kVAh
2F
A0
312343
Total active Energy (3)
4
Float
kWh
30
36
312345
Total reactive Energy (3)
4
Float
kVArh
30
38
312397
Net Total Active Energy
4
Float
kWh
30
6C
312399
Net Total Reactive Energy
4
Float
kVArh
30
6E
Note:
(1). The power factor value indicates the direction of the current. Positive value refers to forward current, negative
value refers to reverse current.
For example, PF=0.98, it means the current is forward flow;
if PF= -0.98, it means the current is reverse flow.
(2). The power sum demand calculation is based on total power = import power – export power.
(3). Total Energy = Import energy + Export energy. For example: total active energy = import active energy + export
active energy
(4). Net Energy = Import energy Export energy. For example: Net active energy = import active energy – export
active erergy
4.2.2 Holding Register, Function code (Hex): 03(read) / 10(write)
Address
Register
Parameter
Modbus
Protocol
Start Address
Hex
Valid range
Mode
High
Byte
Low
Byte
40001
Demand
Time
00
00
Read minutes into first demand calculation. When the
Demand Time reaches the Demand Period then the
demand values are valid.
Length : 4 byte
Data Format : Float
ro