SDM630MCT-ML User Manual V1.2
Total import active energy
Total export active energy
Total import reactive energy
Total export reactive energy
Total reactive Energy (3)
Note:
(1). The power factor value indicates the direction of the current. Positive value refers to forward current, negative
value refers to reverse current.
For example, PF=0.98, it means the current is forward flow;
if PF= -0.98, it means the current is reverse flow.
(2). The power sum demand calculation is based on total power = import power – export power.
(3). Total Energy = Import energy + Export energy. For example: total active energy = import active energy + export
active energy
(4). Net Energy = Import energy – Export energy. For example: Net active energy = import active energy – export
active erergy
4.3.2Holding Register,Function code (Hex) : 03(reade) / 10(write)
Modbus
Protocol
Start
Address Hex
Read minutes into first demand calculation. When the
Demand Time reaches the Demand Period then the
demand values are valid.
Length : 4 byte
Data Format : Float
Write demand period: 0~60 minutes, Default 60.
Range: 0~60, 0 means function closed
Length : 4 byte
Data Format : Float
Default 1, min.
Range :1 ~ (Demand Period -1).
Length : 4 byte
Data Format : Float
Write system type:
1 = 1P2W;
2 = 3P3W;
3 = 3P4W,(default);
4 = 1P3W;
Length : 4 byte
Data Format : Float
(KPPA is asked)
Key
Parameter
Programming
Authorization
(KPPA)
Read: to get the status of the KPPA
0 = not authorized;1 = authorized
Write the correct password to get KPPA, enable to
program key parameters.
Length : 4 byte
Data Format : Float
Write the network port parity/stop bits for MODBUS