SDM630MCT-ML User Manual V1.2
- 2 -
Chapter 2. Technical Parameters
2.1Technical parameters
Voltage AC (Un): 3*230/400VAC
Voltage range: 50 - 600VAC
Auxiliary power supply: 85 - 300VAC
Current input:
Primary current input: 1 - 9999A
Secondary current input: 100mV (optional100mA)
Overcurrent withstand: 20Imax for 0.5s
Frequency:
Rated value: 50/60Hz
Range: 45 - 65Hz
Voltage withstand:
AC voltage withstand: 4KV/1min
Impulse voltage withstand: 6kV – 1.2µS waveform
Power consumption: ≤ 2W/10VA
Display: LCD with white backlit
Max. reading: 99999999 kWh/kVArh
2.2 Accuracy
Voltage: 0.5%
Current: 0.5%
Frequency: 0.2%
Power factor: 1%
Active power: 1%
Reactive power: 1%
Apparent power: 1%
Active energy: Class1
Reactive energy: Class2
2.3 RS485 communication
Bus type: RS485
Protocol: Modbus RTU
Baud rate: 2400/4800/9600(default)/19200/38400bps
Address range: 1-247
Max. Bus loading: 64pcs
Communication distance: 1000m
Parity: EVEN/ODD/NONE (default
Data bit: 8
Stop bit: 1