Eastron SDM630MCT V2 - PT; Secondary PT setting; Set PT ratios value

Eastron SDM630MCT V2
29 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
B+G e-tech and EASTRON SDM630MCT V2 User Manual
B+G e-tech GmbH www.stromzähler.eu info@bg-etech.de
- 13 -
PT
The PT option sets the secondary voltage (PT2 100 to 500V) of the Voltage transformer (PT) that
wires to the meter.
1
From the Set-up menu, use and
buttons to select the PT option.
The screen will show the voltage PT
secondary voltage value. The default
value is 400V
2
Secondary PT setting
Press to enter the PT
secondary voltage selection routine. The
range is from 100 to 500V
3
Set PT ratios value
Press to enter the PT ratio
screen.
The range is from 0001 to 9999
For example, if set the ratio to be 100,it means the primary voltage equals secondary
voltagex100
Pulse output
This option allows you to configure the pulse output. The output can be set to provide a pulse for
a defined amount of energy active or reactive.
Use this section to set up the pulse output 1Units: Total kWh, Total kVArh
1
From the Set-up menu, use and
buttons to select the Pulse
output option.