B+G e-tech EASTRON SDM72D-M User Manual V1.5 English version
B+G e-tech GmbH www.eastron-germany.de Seite 16 von 16
Data Format : Float
40029
15
Network Baud Rate
00
1C
Write the network port baud rate for
MODBUS Protocol, where:
0 = 2400 baud.
1 = 4800 baud.
2 = 9600 baud ( default).
5 = 1200 band
Length : 4 byte
Data Format : Float
r/w
40059
30
Time for scrolling
display
00
3A
Default: 0, Unit: s
Range: 0~30, ( 0 means close scrolling)
Length : 4 byte
Data Format : Float
r/w
40061
31
Time of back light
00
3C
Default: 0. Unit: min
Rang :0~120. ( 0 means the back light will
work all the time )
Length : 4byte
Data Format : Float
r/w
461457
30729
Reset
F0
10
00 03reset the resettable energy
Length : 2 byte
Data Format:Hex
wo

Related product manuals