EasyManua.ls Logo

Eaton 150VCP-WG50 - Tools and Accessories; Type VCP-W Vacuum Circuit Breaker Element Weights (Tables 3.1 and 3.2)

Eaton 150VCP-WG50
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
I.B. 32-255-1G
Page 9
Effective 12/02
3-5 TOOLS AND ACCESSORIES
Tools and accessories, both standard and optional are
available for use with the circuit breaker element (Figure
3-1).
Spin-Free Levering-In Crank: Used to crank breaker
between TEST and CONNECTED positions (Style
701B601G11).
Standard Levering-In Crank: (Style 701B601G12).
Maintenance Tool: Used to charge closing springs
manually (Style 8064A02G11).
Extension Rails: Permits breaker to be withdrawn from
its compartment (Style 7813C41G03 for VCP-W and
VCPW-SE) and (Style 7813C41G04 for VCPW-ND).
Rail Clamps: Used to secure breaker to extension rails
(Style 6511C83G11 for VCP-W and VCP-SE) and (Style
6511C83G02 for VCPW-ND).
Lifting Yoke: Used to lift breaker (Style 691C607G11
for VCP-W and VCPW-SE) and (Style 691C607G02 for
VCPW-ND).
Drawout Ramp: Used to insert or withdraw breaker
from lower compartment without portable lifter (Style
1C14163G02 for VCP-W and VCPW-SE) and (Style
1C14163G01 for VCPW-ND).
Portable Lifter: Used to lift breaker to or from extend-
ed rails (Style 1C14504H01).
Docking Transport Dolly: Used to insert or withdraw
breaker from lower compartment without portable lifter
or move breaker from one location to another (Style
6510C71G11 for VCP-W and VCPW-SE) and (Style
6510C71G02 for VCPW-ND).
Electrical Levering-In Device: Used to electrically
move breaker between TEST and CONNECTED posi-
tions (Style 1A30257G01).
Test Jumper: Used to operate breaker electrically
while breaker is on extension rails or transport dolly
(Style 6526C23G11 for VCP-W and VCPW-SE) and
(Style 1C15331G01 for VCPW-ND).
Test Cabinet: Used to provide power to operate break-
er outside its compartment (Styles 8346A28G21 – G23
for VCP-W and VCPW-SE depending upon voltage
requirements) and (Styles 8346A28G41 – 43 for VCPW-
ND depending upon voltage requirements).
Table 3.1 VCP-W ANSI Rated Breaker Weights
Rating Amperes Lbs. (kg)
50VCPW-ND250 1200 345 (157)
50VCP-W250 1200 350 (159)
50VCPW-SE250 2000 410 (186)
3000 525 (238)
50VCP-W350 1200 460 (209)
50VCPW-SE350 2000 490 (222)
3000 525 (238)
75VCP-W500 1200 375 (170)
75VCPW-SE500 2000 410 (186)
3000 525 (238)
150VCP-W500 1200 350 (159)
150VCPW-SE500 2000 410 (186)
3000 525 (238)
150VCP-W750 1200 350 (159)
150VCPW-SE750 2000 410 (186)
3000 525 (238)
150VCP-W1000 1200 460 (209)
150VCPW-SE1000 2000 490 (222)
3000 525 (238)
150VCP-W1500
(63)
1200 525 (238)
150VCPW-SE1500
(63)
2000 530 (241)
3000 550 (250)
270VCP-W750
(16)
600 460 (209)
1200 480 (218)
2000 500 (227)
270VCP-W1000
(22)
600 460 (209)
1200 480 (218)
2000 500 (227)
270VCP-W1250
(25)
600 460 (209)
1200 480 (218)
2000 500 (227)
270VCP-W1600
(32)
1200 545 (245)
2000 560 (252)
270VCP-W2000
(40)
1200 545 (245)
2000 560 (252)
3-6 TYPE VCP-W VACUUM CIRCUIT BREAKER
ELEMENT WEIGHTS (TABLES 3.1 AND 3.2)
Does not include shipping carton.