6-11 TROUBLESHOOTING CHART (Continued Next Page)
SYMPTOM INSPECTION AREA PROBABLE DEFECTS
Fails To Close
Closing Springs not charged Control Circuit Control Power
(fuse blown or switch off)
Secondary Disconnects
Motor Cut-off Switch
(Poor or burned contacts,
Lever not operational)
Terminals and connectors
(Poor or burned contacts)
Motor
(Brushes worn or commutator
segment open)
Mechanism Pawls
(Slipping or Broken)
Ratchet Wheel
(Teeth worn or broken)
Cam Shaft Assembly
(Sluggish or jammed)
Oscillator
(Reset spring off or broken)
Closing Spring charged but No Closing Sound Control Power
breaker does not close (Close Coil does (Fuse blown or switch off)
not pick up)
Secondary
Disconnects
Anti-Pump Relay
(Y relay N. C. contact open or
burned or relay picks up)
Close Coil
(Open or burned)
Latch Check Switch
(Contact open-bad switch or
trip bar not reset)
Auxiliary Switch
(b contact open or burned)
Motor Cut-off
(Contacts open or burned)
Trip Coil Assembly
(Clapper fails to reset)