SPECIFICATIONS
Eaton 5125 Tower UPS (1000–2200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality
51
Table 6. Environmental and Safety
Low Voltage Models High Voltage Models
Operating Temperature 10°C to 40°C (50°F to 104°F)
Optimal battery performance: 25°C (77°F)
Storage Temperature 0°C to 25°C (32°F to 77°F)
Transit Temperature -25°C to 55°C (-13°F to 131°F)
Relative Humidity 5–95% noncondensing
Operating Altitude Up to 3,000 meters above sea level
Transit Altitude Up to 15,000 meters above sea level
Audible Noise Less than 40 dBA Normal mode, typical load
Less than 55 dBA Battery mode
Surge Suppression ANSI C62.41 Category B, IEC 61000-4-5
Safety Conformance UL 1778 4th Edition, UL 497A;
CSA C22.2, No. 107.3;
NOM-019-SCFI
UL 1778 4th Edition, UL 497A (data line only);
CSA C22.2, No. 107.3;
IEC/EN 62040-1-1 and IEC/EN 60950
Agency Markings cULus, cUL, NOM cULus and cUL; CE, C-Tick, LGA/GS, UL-GS
EMC (Class A) FCC Part 15, ICES-003, VCCI IEC/EN 62040-2, FCC Part 15, ICES-003
Table 7. Battery
UPS Configuration 1000 VA: (2) 24V, 9 Ah internal batteries
1500 VA: (4) 48V, 7 Ah internal batteries
2200 VA: (4) 48V, 12 Ah internal batteries
EBM Configuration PW5125 EBM-24: (8) 24V, 9 Ah batteries
PW5125 EBM-48: (8) 48V, 9 Ah batteries
Type Sealed, maintenance‐free, valve‐regulated, lead‐acid
Charging Internal battery: approximately 3 hours to 90% usable capacity
at nominal line voltage after full load discharge
External battery: recharging at 80% load or less is recommended;
no more than 16x discharge time to 90% usable capacity at nominal line voltage after full
load discharge; an external battery charger is recommended for faster recharge times
when using more than two EBMs.
Monitoring Advanced monitoring for earlier failure detection and warning;
auto detection of additional EBMs