2. Presentation
Description Available settings Default settings
In/Out settings
Load segments
- Auto shutdown
delay
[Disable] [0s] [1 s] [2 s]…[65354 s]
During a power outage, authorises
to keep some equipment running
while turning off other equipment.
This feature allows to save battery
power.
Group 1: Disable
Group 2: Disable
Overload pre-
alarm
[5 %] [10 %] [15 %] [20 %] ... [100 %]
[105 %]
Gives a warning when a predefined
critical percentage of load is
reached.
[105 %]
ON/OFF settings
Cold start [Disable] [Enable]
Authorises the product to start on
battery power.
Enable
Forced reboot [Disable] [Enable]
If set to Enable, when a shutdown
sequence is sent through
communication port, it allows,
if mains recovers during the
sequence, to shutoff the output
during 10 s.
Enable
Auto restart [Disable] [Enable]
Authorises the product to restart
automatically when mains recovers
after a complete battery discharge.
Enable
Energy saving [Disable] [Enable]
If Enable, UPS will shutdown after
5min of back-up time, if no load is
detected on the output.
Disable
Sleep mode [Disable] [Enable]
If disable, LCD and communication
will turn OFF immediately after
UPS is OFF.
If enable, LCD and communication
stays ON 1h30 min after UPS is OFF.
Disable
Remote command [Disable] [Enable]
If enable, shutdown or restart
commands from software are
authorised.
Enable
Battery settings
Automatic battery
test
[No test] [Every day] [Every week]
[Every month]
Available only if battery charge
mode is set to constant charge.
Every week
(in constant charge,
otherwise following ABM
battery test method)
Low battery warn-
ing
[10 %] [20 %] [30 %] [40 %] [50 %]
[60 %] [70 %] [80 %] [90 %]
The alarm triggers when the set
percentage of battery capacity is
reached during a back-up time.
20 %
Restart battery
level
[10 %] [20 %] [30 %] [40 %] [50 %]
[60 %] [70 %] [80 %] [90 %] [100 %]
If set, automatic restart will occur
only when percentage of battery
charge is reached.
0 %
Battery charge
mode
[ABM cycling] [Constant charge] ABM cycling
EBM number
setting
[0] [1] [2] [3] [4]
Using standard EBM, UPS detects
automatically the amount of EBM
connected.
EBM automatic detection,
otherwise 0
Deep discharge
protection
[Yes] [No]
If set to Yes, the UPS automatically
prevents battery from deep
discharge by adapting end of
back-up time voltage threshold.
Yes