Programmable signal outputs
The5PX incorporates several programmable signal outputs: one relay output and two optocoupler outputs (DB9 pins 1
and 8).Signal outputs can be configured (see Settings > Comm settings > Output Signals) to report thefollowing
information:
Signal
Default assignment
Description
On battery (On Bat) DB9-Pin 8 UPS is in battery mode
Low battery (Low Bat) DB9-Pin 1
UPS is in battery mode and has reached the low
battery alarm threshold
Battery fault
(1) Relay output
Battery fault
UPS OK DB9-Pin 7
Load is powered with no alarm
Load protected -
UPS is on inverter, with no alarm and ready to go to
battery
Load powered -
Load is powered
General alarm -
Choose events that will trigger this alarm trough
the LCD (Settings > Comm settings > General
alarm).
For more information on possible events please
look at User settings
OVL pre-alarm - Overload pre-alarm
Bat disconn - Battery is disconnected
(1) Relay output: