614-40094-00
15
1.Connect the input socket (48) onthe HotSwap MBP
module to theAC power source using the cable(13)
supplied.
2.Connect the UPS input socket (2)to the “UPS
Input” (47) on theHotSwap MBP module, using thecable
(26) supplied. This cableand the connector are
markedblue.
3.Connect the UPS outlet (3) to the “UPS Output” (46)
on the HotSwap MBP module, using the cable (26)
supplied. This cable and the connector are marked in
red.
4. Connect the equipment to the outlets(42) on the
HotSwapMBP module.
These outlets differ,depending on the version of
theHotSwap MBP module.
Caution :Do not use UPS outlets(4) to supply
equipmentbecause use of switch (45) on theHotSwap
MBP module would cutsupply to the equipment.
HotSwap MBP module operation
The HotSwap MBP module has a rotaryswitch (45) with
two positions:
Normal: the load is supplied by the UPS,LED (43) is on.
Bypass: the load is supplied directly bythe AC power
source. LED (44)is on.Load is not protected.
UPS start-up with the HotSwap MBP module
1. Check that the UPS is correctly connected to the HotSwap MBP module.
2.Start the UPS by pressing the button on the UPScontrol panel. LED (43) "UPS ON - OK to switch"on the HotSwap
MBP module goes ON (otherwise,there is a connection errorbetween the HotSwap MBP module and the UPS).
3. Set switch (45) to Normal position.The red LED onthe HotSwap MBP module goes OFF.
HotSwap MBP module test
1. Set switch (45) to Bypass position and check that the load is still supplied.
2. Set switch (45) back to Normal position.