Chapter 2 — Mounting
The SVX9000/SPX9000 drive may be mounted side-by-side or stacked vertically, as outlined
in the following section.
Space Requirements
To ensure proper air circulation and cooling, follow the guidelines below.
Table 2-1: Space Requirements for Mounting a SVX9000/SPX9000 Drive
Dimensions represent the minimum clearance needed when mounting a SVX9000/SPX9000. See Figure 2-1 below.
A = clearance around the SVX9000/SPX9000.
A
2
= clearance needed to change the fan without disconnecting the motor cables.
B = distance between adjacent SVX9000/SPX9000 drives or between the SVX9000/SPX9000 and an enclosure wall.
C = clearance above the SVX9000/SPX9000.
D = clearance below the SVX9000/SPX9000.
Minimum clearance below the SVX9000/SPX9000 needed to change the fan.
Figure 2-1: Mounting Space Requirements.
If several units are mounted above each other, the clearance between the drives should equal
C + D (see Table 2-1 and Figure 2-1 above). In addition, the outlet air used for cooling the
lower unit must be directed away from the inlet air used by the upper unit.
Frame Drive Type
Dimensions in Inches (mm)
AA
2
BCD
4 230V, 1 – 3 hp I
L
, 3/4 – 3 hp I
H
480V, 1 – 5 hp I
H
, 1-1/2 – 7-1/2 hp I
L
0.8
(20)
0.8
(20)
3.9 (100) 2.0
(50)
5 230V, 5 – 10 hp I
L
, 5 – 7-1/2 hp I
H
480V, 7-1/2 – 15 hp I
H
, 10 – 20 hp I
L
1.2
(30)
0.8
(20)
4.7 (120) 2.4
(60)
6 230V, 15 – 20 hp I
L
, 10 – 15 hp I
H
480V, 20 – 30 hp I
H
, 25 – 40 hp I
L
575V, 2 – 25 hp I
H
, 3 – 30 hp I
L
1.2
(30)
0.8
(20)
6.3 (160) 3.1
(80)
7 230V, 25 – 40 hp I
L
, 20 – 30 hp I
H
480V, 40 – 60 hp I
H
, 50 – 75 hp I
L
575V, 30 – 40 hp I
H
, 40 – 50 hp I
L
3.1
(80)
3.1
(80)
11.8
(300)
3.9 (100)
8 480V, 75 – 125 hp I
H
, 100 – 150 hp I
L
575V, 50 – 75 hp I
H
, 60 – 100 hp I
L
3.1
(80)
5.9 (150) 3.1
(80)
11.8
(300)
7.9 (200)
9 480V, 200 – 250 hp I
L
, 150 – 200 hp I
H
575V, 100 – 150 hp I
H
, 150 – 200 hp I
L
2.0
(50)
3.1
(80)
15.7
(400)
9.8 (250)
13.8
(350)
D