INSTALLATION
Eaton
®
9140 (9910-E82/E83) UPS Installation Guide for IBM
®
Applications S 164201715 Rev 2
www.eaton.com/ibm
38
Table 8. Typical Power Connections (Figure 30–Figure 32)
Item Description
1 IEC60309 Plug [E82: 60A 2P+G (360P6W); E83: 63A P+N+G (363P6W)]
2 IEC60309 Receptacle [E82: 60A 2P+G (360R6W); E83: 63A P+N+G (363R6W)]
3 IEC 320-C19 16A
4 IEC 320-C20 16A
5 PDU to UPS Power Cords
UPS IBM FC Plug Type Supplier Description
E82 6492 IEC60309 60A 2P+G IBM Burndy
®
to IEC60309 60A 2P+G Plug, 4.3m/14 ft
E83 6491 IEC60309 63A P+N+G IBM Burndy to IEC60309 63A P+N+G Plug, 4.3m/14 ft
6 E82/E83 2974* — Eaton Burndy to IEC 320-C20, 1.8m/6 ft
7 Burndy UTG Connector
* Using 2974 limits the PDU to 16A.
NOTE E82/E83 does not support iSeries PDU 5150, 5161, 5162, 9176 or 9177.
IBM (5)
11
PDU
IBM
iSeries
or
pSeries 7188,
9188, 5889, or
7109
Device
E82/E83
8000W
UPS
2 2
Mains
77
3
3
3
3
Figure 30. E82/E83 with Non-Redundant Power