OPERATION
Eaton
®
9140 (9910-E82/E83) UPS Installation Guide for IBM
®
Applications S 164201715 Rev 2
www.eaton.com/ibm
42
The following table shows the indicator status and description.
Indicator Status Description
Green
On The UPS is operating normally.
Slow Flash The UPS is in Standby mode.
Fast Flash The UPS is starting up.
Off The UPS is turned off and will not turn on automatically.
Yellow
On The UPS is in Battery mode.
Slow Flash The UPS is in Battery mode and a Low Battery condition is detected.
Fast Flash A battery test is in progress.
Yellow
On The UPS is in Bypass mode.
Slow Flash Bypass mode in unavailable because the input utility is outside the configured
bypass range.
Red
Slow Flash The UPS has an active warning alarm and is supporting the load.
See “Troubleshooting” in the Eaton 9140 UPS (7.5–10 kVA) User's Guide on the
User's Guide CD for additional information.
All LEDs
Slow Flash The UPS is powering down and the load is no longer supported.
Changing the Language
To change the language setting, select MENU from the system status
screen, then select SETUP, USER SETUP, and LANGUAGE. Scroll
through the available options and press the
button to select the
language.