OPERATION
Eaton
®
9140 (9910-E82/E83) UPS Installation Guide for IBM
®
Applications S 164201715 Rev 2
www.eaton.com/ibm
44
User Settings
The following table displays the options that can be changed by the
user.
Table 10. User Settings
Description Available Settings Default Setting
O/P (Output) Frequency* [50 Hz][60 Hz][Auto]
NOTE If Auto is selected, input frequencies
<55 Hz are set to 50 Hz, and input frequencies
>
55 Hz are set to 60 Hz. O/P Frequency
changes from Auto to the sensed frequency
setting.
Auto
O/P (Output) Voltage [200V][208V][220V][230V][240V][Auto]
NOTE If Auto is selected, input voltages
<220V are set to 208V, and input voltages
>
220V are set to 230V. O/P Voltage changes
from Auto to the sensed voltage setting.
Auto
Buzzer Alarm [Enabled][Disabled] Enabled
Battery Pack 1 through 5
NOTE A value of 1 indicates the UPS internal
batteries only. See “Configuring the UPS for
EBMs” on page 52.
1
Battery Test [Enabled][Disabled]
NOTE When Enabled, the battery test runs
automatically approximately every three
months.
Enabled
DC Start [Enabled][Disabled] Shipped: Disabled
After one startup and
shutdown sequence: Enabled
Auto Restart [Enabled][Disabled] Enabled
UPS ID 0 through 3
NOTE This option is not used.
0
* Changes to these options should be made before turning on the UPS (while the UPS is in Standby mode); otherwise,
the changes do not take effect.