UPS INSTALLATION
Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide S 164201642 Rev C www.eaton.com/powerquality
26
Table 4. Input/Output Terminal Connector Construction
10 kVA Recommended Terminal Ring Lug Tool
Terminal Ring Lug Type Hand Crimping Tool
L1, L2, L3 Molex/ETC P/N 19071-0136 Molex/ETC P/N 640013900
Neutral Molex/ETC P/N 19071-0148 Molex/ETC P/N 640013900
Ground Molex/ETC P/N 19070-0150 Molex/ETC P/N 640010300
15 kVA Recommended Terminal Ring Lug Tool
Terminal Ring Lug Type Hand Crimping Tool
L1, L2, L3 Molex/ETC P/N 19071-0250 Molex/ETC P/N 640013900
Neutral Molex/ETC P/N 19071-0253 Molex/ETC P/N 640013900
Ground Molex/ETC P/N 19070-0150 Molex/ETC P/N 640010300
To construct terminal connectors for L1, L2, L3, and Neutral:
1. Strip wire to a length of 11.18–12.70 cm (0.44–0.50 in). Do not nick or cut the wire strands.
2. Verify that wire sizes stamped on the terminal lug and the tool's crimping head match.
3. Insert the stripped wire into the terminal wire barrel. The end of the conductor must not protrude more than 1.6
mm (.063 in) beyond the edge of the wire barrel.
4. Place the terminal lug in the stationary die with the edge of the wire barrel resting against the locator and the
bottom of the terminal tongue facing the stationary die.
5. Holding the wire in place, activate the tool or power unit to complete the crimp.
6. Inspect the crimped terminal to ensure the wire is fully inserted and flush with the end of the wire barrel, and the
crimp is centered on the wire barrel. Do not use crimped terminals that do not meet these standards.
To construct terminal connectors for Ground:
1. Strip wire to a length of 7.95–8.74 cm (0.313–0.344 in). Do not nick or cut the wire strands.
2. Verify that wire sizes stamped on the terminal lug and the tool's crimping head match (10 AWG).
3. Place the terminal lug in the stationary die with the edge of the wire barrel resting against the locator and the
bottom of the terminal tongue facing the stationary die.
4. Close the tool handles until the terminal is held firmly in place.
5. Insert the stripped wire into the insulation barrel until the wire butts against the locator.
6. Complete the crimp by closing the tool handles until the ratchet releases.
7. Allow the tool handle to fully open and remove the crimped terminal.
6. Inspect the crimped terminal to ensure the wire is fully inserted and flush with the end of the wire barrel, and the
crimp is centered on the wire barrel. Do not use crimped terminals that do not meet these standards.