Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide S 164201642 Rev C www.eaton.com/powerquality
64
To install an RMP:
NOTE If mounting to a hollow wall, secure the enclosure bottom to a wood or metal stud
within the wall. Do not use hollow wall anchors. The RMP can also be mounted to a single- or
double-gang electrical box.
1. If wall mounting, securely mount the RMP. Continue to Step 2.
If desk mounting, install the provided bumpers to the bottom of the
RMP enclosure. Proceed to Step 3.
2. Install 1/2 conduit from the RMP to the IRC through the cable exit
openings (see Figure 36). Proceed to Step 4.
3. Install wiring from the RMP to the IRC using the cable listed in
Table 6 and the provided strain relief bushings in the cable exit
openings in the IRC (see Figure 38) and the RMP.
4. Connect the wiring between the RMP and the IRC plug‐in terminal
blocks using terminations shown in Table 6. See Figure 37 and
Figure 38 for plug‐in terminal block locations.
Table 6. RMP Wire Terminations
From RMP Terminal To IRC Terminal Remarks
J1-1 J1-1
Use Beldon 8690 060 or
equivalent cable
J1-3 J1-3
J1-4 J1-4
J1-5 J1-5
J1-6 J1-6
5. Install the IRC into an open X-Slot communication bay (see
page 56).