EasyManua.ls Logo

Eaton 9355 - Page 111

Eaton 9355
120 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Eaton 9355 UPS (10/15 kVA) User’s Guide 164201594—Rev H0 99
CChhaapptteerr 88 UUPPSS MMaaiinntteennaannccee
This section explains how to:
Care for the UPS and batteries
Recycle used batteries or UPS
Use the maintenance bypass switch
88..11 UUPPSS aanndd BBaatttteerryy CCaarree
For the best preventive maintenance, keep the area around the UPS clean and dust–free. If the atmosphere is
very dusty, clean the outside of the system with a vacuum cleaner.
For full battery life, keep the UPS at an ambient temperature of 77°F (25°C).
NOTE The batteries in the UPS are rated for a 3–5 year service life. The length of service life
varies, depending on the frequency of usage and ambient temperature. Batteries used
beyond expected service life will often have severely reduced runtimes. Replace
batteries at least every 5 years to keep units running at peak efficiency.
88..11..11 SSttoorriinngg tthhee UUPPSS aanndd BBaatttteerriieess
When storing the UPS and optional cabinets, the following requirements should be met:
Verify that the battery circuit breaker is in the OFF position.
Avoid temperature and humidity extremes. To maximize battery life, the recommended storage
temperature is 59°F (15°C) to 77°F (25°C).
If you store the UPS for a long period, recharge the batteries every 10 months by applying utility power.
The batteries charge to 80% capacity in approximately 3 hours. However, it is recommended that the
batteries charge for 48 hours after long-term storage.
Check the battery recharge date on the shipping carton label. If the date has expired and the batteries
were never recharged, do not use the UPS. Contact your service representative.
88..22 WWhheenn ttoo RReeppllaaccee BBaatttteerriieess
When the
OPERATION
Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev D
87
Normal Mode Startup
To start up the UPS when the load is de-energized:
1. If an optional wall-mounted bypass c abinet is installed, proceed to
Step 2; otherwise, proceed to Step 4.
2. Verify the wall mounted bypass is transfered to UPS mode (see
“Using the Wall-Mounted Bypass Cabinet” on page 97.
3. Proceed to Step 4.
4. Verify that the internal maintenance bypass switc h is in the UPS
position(seeFigure59onpage95).
5. If an optional isolation transformer is installed, switch the input
circuitbreakertotheONposition(seeFigure12onpage21).
6. Switch on utility power where the UPS is connected.
7. Wait for the front panel LCD to illuminate.
The
indicator flashes.
8. Remove the breaker tie from all battery circuit breakers.
9. Switch all battery circuit breakers to the ON position.
The
indicator stops flashing.
10. Press a ny button on the front panel display to activate the menu
options.
11. Press the
button on the front panel display a nd then press the
button to select the TURN UPS ON/OFF menu.
12. Select the TURN UPS ON option. Press and hold the
button for
three seconds, until the UPS stops beeping.
The
indicator illuminates. The UPS is now powering the load.
If the
indicator is flashing, check the UPS status from the front
panel to view the active alarms. Correct the alarms and restart if
necessary.
indicator flashes and the LCD panel displays Battery Failure, the batteries may need replacing.
Contact your service representative to order new batteries.
Change the batteries approximately every five years.
88..33 RReeccyycclliinngg tthhee UUsseedd BBaatttteerryy oorr UUPPSS
Contact your local recycling or hazardous waste center for information on proper disposal of the used battery or
UPS.
WARNING
Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal of batteries is
required. Refer to your local codes for disposal requirements.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It
may be toxic.

Table of Contents

Other manuals for Eaton 9355

Related product manuals