12 Eaton 93PM Emergency Lighting UPS (50 kW, 480V Three and Four-Wire UL 924) Installation and Operation Manual P-164000569—Rev 03
CAUTION
If battery systems are located in the same room as the UPS, the battery manufacturer's environmental
requirements should be followed if they are more stringent than the UPS requirements. Operating
temperatures above the recommended range will result in decreased battery life and performance, and may
reduce or void the battery warranty.
The UPS ventilation requirements are shown in Table 2.
To allow for future power upgrades, Eaton recommends using air conditioning or ventilation sized for the fully
rated UPS kW frame size installed instead of the derated kW ordered. Sizing the site cooling infrastructure to
be capable of cooling the maximum kW frame size will allow a full power rating upgrade without having to
modify the infrastructure.
NOTE The battery system’s capacity must also be considered when planning for future power
upgrades. The battery system must either be sized to the anticipated future rating or
upgraded with the power upgrade. See Table 1 for battery cabinet requirements.
Table 2. Air Conditioning or Ventilation Requirements During Full Load Operation
Model
UPS
Rating
Input/Output Voltage
Heat Rejection BTU/hr
x1000 (kg-cal/hr)
Minimum Required
Cooling Air Flow
Eaton 93PM-50-1 20 kW
480/480 2.55 (643)
189 liter/sec (400 cfm)
Eaton 93PM-50-1 30 kW
480/480 3.58 (903)
Eaton 93PM-50-1 40 kW
480/480 4.56 (1150)
The UPS equipment operating environment must meet the weight requirements shown in Table 3 and the size
requirements shown in Figure 3 through Figure 9. Dimensions are in millimeters (inches).
NOTE Refer to the Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass Installation and
Operation (50 kW and 100 kW SIAC-B) Manual, listed in paragraph
1.8 For More Information, for Sidecar Integrated Accessory Cabinet-Bypass (SIAC-B)
size requirements.
Table 3. UPS Cabinet Weights
Model
Weight kg (lb)
Frame
Shipping
Installed
Point Loading
Eaton 93PM-50-1
Capacity
338 (745) 318 (702) 4 at 80 (176)
Eaton 93PM-50-1 with UPS Top Entry Wiring Sidecar (no
breakers)
Capacity
425 (937) 402 (887) 4 at 101 (222)
Eaton 93PM-50-1 with SIAC-B (4-Breaker)
Capacity
460 (1014) 429 (947) 4 at 107 (237)
The UPS cabinet uses forced air cooling to regulate internal component temperature. Air inlets are in the front
of the cabinet and outlets are on top or in the back of the cabinet. Allow clearance in front of and on top or in
back of the cabinet for proper air circulation. The clearances required around the UPS cabinet are shown in
Table 4.
UPS Installation Plan and Unpacking