Installation
4-18 Eaton 93PM Integrated Battery Cabinet-Small Welded (IBC-SW) Installation Manual P-164000639—Rev 1 www.eaton.com/powerquality
Table 4-2. Eaton 93PM IBC–SW TB2 Interface Wiring Terminal Block Terminations
Terminal Function
Size of Pressure
Termination
Tightening Torque
Nm (lb in)
Type Screw Comments
Shunt Trip #26–#16 0.4 (3.5) - 0.8 (7.1) Slotted Use #18 AWG twisted-pair wires for each input and
return or common.
Strip wire insulation back
10 millimeters to wire terminal blocks.
Use wire rated for 600V and Class 1 wiring methods.
Battery Detect #26–#16 0.4 (3.5) - 0.8 (7.1) Slotted Use #18 AWG twisted-pair wires for each input and
return or common.
Strip wire insulation back
10 millimeters to wire terminal blocks.
Thermal Sensor #26–#16 0.4 (3.5) - 0.8 (7.1) Slotted Use #18 AWG twisted-pair wires for each input and
return or common.
Strip wire insulation back
10 millimeters to wire terminal blocks.