Product Specifications
7-2 Eaton 93PM Integrated Battery Cabinet-Small Welded (IBC-SW) Installation Manual P-164000639—Rev 1 www.eaton.com/powerquality
7.2.2 Environmental and Safety Specifications
Operating Temperature The battery cabinet is rated for operation in up to a 40°C (104°F) ambient
temperature.
The batteries are rated for a 25°C (77°F) ambient temperature to extend
their useful life.
Transit Temperature -25°C to 60°C (-13°F to 140°F)
Recommended Eaton PWHR12200W4FR or CSB HRL12200WFR Battery
Transit: -20°C to 50°C (-4°F to 122°F)
Storage Temperature -25°C to 55°C (-13°F to 131°F)
Recommended Eaton PWHR12200W4FR or CSB HRL12200WFR Battery
Storage: -20°C to 50°C (-4°F to 122°F))
Operating Altitude Maximum 1500m (5000 ft) at 40C without derating
Transit Altitude 15000m (49213 ft)
Ventilation Convection
Relative Humidity (operating and
storage)
95%, noncondensing
Acoustical Noise Not applicable
Safety Conformance UL1778 4
th
edition
Agency Markings cULus
EMC (Class A) FCC Part 15 Class A and 62040-2 c3