Eaton 93PR 500 kW UPS
User's and Installation Guide
38
93PR-600
UPS 1
93PR-600
UPS 2
93PR-600
UPS 3
93PR-600
UPS 4
External
Battery
Cabinet
External Battery Switch
Load
Figure 4-3: Common Battery Configurations
The DC input voltage for 93PR is 400Vdc~580Vdc. 93PR support various DC source including VRLA, Lithium-
ion, Ni-Cad, Supercaps and flywheel. For Lithium-ion battery application, battery BTR and detail information
shall refer to the battery’s own BMS. Or you can contact Eaton for more integration application of BMS data