Eaton 93PR 500 kW UPS
User's and Installation Guide
77
8.5. UPS Environmental Specifications
Table 8-5: UPS environmental specifications
Ambient Service Temperature Range, (UPS)
From+0 °C to +40 °C*,
No output power derating required.
Ambient UPS Storage Temperature Range
From -25 °C to +55 °C in the protective package*
Maximum Service Altitude
Maximum 2000 m (6600 ft) with 1 % derating per each
additional 100 m.
Relative Humidity Range
5 to 95 %, no condensation allowed
Acoustic Noise at 1 m
65 dBA~75 dBA
EMC
IEC 62040-2 C3
*Maximum recommended operating and storage temperature with VRLA batteries is +25 °C.
Storage condition for UPS and spare parts store one year (refer unit SN).
Place
Indoor
Dusty
Well
Storage Temperature
<40°C
Storage Humidity
< 70% RH
Other
With original package
Please re –evaluate the storage time if can not meet above storage condition.