Loading...
The following UPS configurations with different static bypass sizes and number
of UPMs are possible:
Table 2: UPS configurations
Description
System
power
[kW]
Power
modules
[kW]
Static
switch
[kW]
Internal battery
Single system configurations in the 20 kW frame size*
93PS-8(20)-20(-C) 8 1*8 20 Yes/No
93PS-8(20S)-20(-C) 8 1*8 40 Yes/No
93PS-10(20)-20(-C) 10 1*10 20 Yes/No
93PS-10(20S)-20(-C) 10 1*10 40 Yes/No
93PS-15(20)-20(-C) 15 1*15 20 Yes/No
93PS-15(20S)-20(-C) 15 1*15 40 Yes/No
93PS-20(20)-20(-C) 20 1*20 20 Yes/No
93PS-20(20S)-20(-C) 20 1*20 40 Yes/No
Single system configurations in the 40 kW frame size
93PS-8(40)-20 8 1*8 40 Yes/No
93PS-8+8(40)-40 8 8+8 40 Yes (separate)/No
93PS-10(40)-20 10 1*10 40 Yes/No
93PS-10+10(40)-40 10 10+10 40 Yes (separate)/No
93PS-15(40)-20 15 1*15 40 Yes/No
93PS-15+15(40)-40 15 15+15 40 Yes (separate)/No
93PS-20(40)-20 20 1*20 40 Yes/No
93PS-20+20(40)-40 20 20+20 40 Yes (separate)/No
93PS-30(40)-40 30 2*15 40 Yes (common)/No
93PS-40(40)-40 40 2*20 40 Yes (common)/No
*Applies to the 93PS 8–20 kW C-model as well.
With a 93PS UPS 40 kW frame, a single UPS frame can house a maximum of 2
UPMs, resulting in the maximum power rating of 40 kW. In addition, up to 4 UPS
frames can be connected in parallel to create even larger systems. With a 93PS
UPS 20 kW frame, a single UPS frame can house only one power module.