OPERATION
Eaton 9910 UPS and EBM User's Guide S P-164000005 Rev 2
29
Transferring the UPS between Modes
(6000 VA models only) You can transfer the UPS between Normal and
Bypass modes.
Transferring from Normal to Bypass Mode
To transfer from Normal to Bypass mode:
1. From the main menu, press the down (
B
) button to scroll to the
Control menu, and press the OK button.
2. Press the down (
B
) button to scroll to Go to Bypass, and press the
OK button. The screen displays Manual Bypass Command Sent.
Transferring from Bypass to Normal Mode
To transfer from Bypass to Normal mode:
1. From the main menu, press the down (
B
) button to scroll to the
Control menu, and press the OK button.
2. Press the down (
B
) button to scroll to Go to Normal, and press the
OK button. The screen displays Normal Mode Command Sent.
Retrieving the Alarm History
To retrieve the alarm history through the display:
1. From the main menu, press the down (
B
) button to scroll to the
Alarm History menu, and press the OK button.
2. Press the down (
B
) button to scroll through the listed events,
notices, and alarms.
3. Press the escape (X) button to return to the previous menu.