OPERATION
Eaton 9910 UPS and EBM User's Guide S P-164000005 Rev 2
32
To set the restart delay times for each load segment:
1. From the main menu, press the down (
) button to select the restart delay for the load
segment. You can specify one of the following options for the
restart delay time for each load segment:
S Select zero seconds to restart immediately.
S Select 1–32767 seconds to delay for the specified time.
S Select Off.
5. Press the OK button for 1 second to confirm.
6. Repeat Step 3 to Step 5 to set the other load segment, if applicable.
NOTE Load segment on/off commands that are issued through the Control menu override
the user settings for load segments.
NOTE A single load segment delay applies to both receptacles. However, there is an
additional automatic 1-second delay between closing segments 1 and 2. The delay is always
present when an On command is issued for both segments at the same time.
Configuring Automatic on Battery Shutdown
You can use the Automatic on Battery Shutdown setting to configure how
soon the load segment shuts down when the UPS transfers to Battery
mode:
S If you select Off (default), the load segment turns off only when you
manually press the button, issue an external command, or turn it off
through the display (Control > Load Segments).