7. UPS maintenance
Replacing the internal battery
The internal battery is heavy. Use caution when handling the heavy batteries.
To replace the battery pack:
1. Remove the center cover of the front panel
2. Remove the two screws to open the left side of the front panel
3. Remove the two screws to pull out the metal protection cover of the battery
A ribbon cable connects the LCD control panel to the UPS. Do not pull on the cable or disconnect it.
4. Pullouttheplastichandleofthebatterypack,andslidethepackoutslowlyontoaatandstable
surface. Use two hands to support the battery pack. See "Recycling the used equipment"
on page 37 for proper disposal.
5. Verify that the replacement batteries have the same rating as the batteries being replaced.
6. PutthenewbatterypackintotheUPS.Pushthebatterypackrmlytoensureaproperconnection.
7. Screw back the metal protection cover and the front panel, then clip the center cover.
8. Continue to “Testing new batteries” on page 36.