Eaton 9PX Lithium-Ion User Guide P-164001006—Rev 02 9
Table 6. User Settings (Continued)
Submenu Available Settings Default Settings
Output mode
Mode: [Industrial] [IT] [Custom] Overload:
[Inv>Stop] [Inv>BP] [Inv>BP>Inv]
[IT] [Inv>BP>Inv]
[Inv>Stop]
Short-circuit: [Inv>Stop] [Inv>BP]
[Inv>BP>Inv]
Input volt hysteresis
Sets input voltage hysteresis from [1] to |10V] [10V]
High Efficiency mode
[Enabled] [Disabled] Power the output from Bypass
for high efficiency
[Disabled]
Bypass settings
[Volt low] [160V] HV;
[Volt high] [[276V] HV;
[Qualify] [In spec];
[Hz synch] [5%];
[Unsynch] [Half cycle]
Load segments
[Auto start delay] UPS: [0s]; Group1: [3s];
Group2: [6s]
[Auto shutdown delay] UPS: [Disabled];
Group1: [Disabled];
Group2: [Disabled]
Overload prealarm [10%] … [102%] Load % when overload alarm
occurs
[102%]
On/Off Settings
Start/Restart
[Cold start] [Auto restart] [Auto start] Cold start] [Auto
restart] are Enabled
[Start on bypass] [Auto start] [Start on
bypass] are Disabled
Forced reboot
[Enabled] [Disabled] [Enabled]
[Timer] [10s] …[180s] [10s]
When mains recover during a shutdown sequence:
If set to Enabled, shutdown sequence will
complete and wait 10 seconds prior to restart, If
set to Disabled, shutdown sequence will not
complete, UPS stays on.
Energy saving
[Enabled] [Disabled] [Disabled]
[Timer] [1min] … [15min] [5min]
[Level] [100W] … [1000W] [100W]
If Enabled, UPS will shut-down after defined
duration. of back-up time, if load is less than set
value.
Sleep mode [Enabled] [Disabled] [Enabled]
User Settings