Submenu Available settings Default settings
In/Out settings
Overload
prealarm
[10%] … [102%]
Load % when overload alarm occurs.
[102%]
On/Off settings
Cold start [Enabled] [Disabled]
Authorize the product to start on
battery power.
[Enabled]
Forced reboot [Enabled] [Disabled]
If mains recover during a shutdown
sequence:
If set to Enabled, shutdown sequence
will complete and wait 10 seconds
prior to restart,
If set to Disabled, shutdown sequence
will not complete and restart will occur
immediately.
[Enabled]
Auto restart [Enabled] [Disabled]
Authorize the product to restart
automatically when mains recovers
after a complete battery discharge.
[Enabled]
Auto start [Enabled] [Disabled]
The UPS automatically starts up as
soon as mains power is available
(no need topress the
button).
[Disabled]
Energy saving [Disabled] [100W] … [1000W]
If Enabled, UPS will shutdown after
5 min. of back-up time, if load is less
than threshold.
[Disabled]
Sleep mode [Enabled] [Disabled]
If Disabled, LCD and communication
will turn OFF immediately after UPS is
OFF.
If Enabled, LCD and communication
stays ON 1h30 min after UPS is OFF.
[Enabled]
Remote com-
mand
[Enabled] [Disabled]
If Enabled, shutdown or restart
commands from software are
authorized.
[Enabled]
Bypass standby [Enabled] [Disabled]
Define if output is powered from
Bypass in Standby mode.
[Disabled]
Remote On/Off [Bypass for MBP] [Enabled] [Disabled]
If set for Bypass for MBP, the UPS will
be forced to static bypass when sig-
naled by the MBP for safe transfer.
If set for Enabled, the UPS can be shut-
down or started by Remote On/Off.
[Bypass for MBP]
Battery settings
Automatic battery
test
In constant charge mode:
[No test] [Every day] [Every week]
[Every month]
In ABM cycling mode :
[No test] [Every ABM cycle]
[Every ABM cycle]
Low battery
warning
[0%] ... [100%]
The alarm triggers when the set
percentage of battery capacity is
reached during back-up time.
[20%]
Restart bat. level [0%] ... [100%]
If set, automatic restart will occur only
when percentage of battery charge is
reached.
[0%]
Battery charge
mode
[ABM cycling] [Constant charge] [ABM cycling]
External battery [Auto detection]
[Manual EBM set.]
[Manual battery set.]
[No battery]
[Auto detection]
Using standard EBM, UPS
detects automatically the
number of EBM connected
Deep Disch.
protect.
[Yes] [No]
If set to Yes, the UPS automatically pre-
vents battery from deep discharge by
adapting end of back-up time
voltage threshold.
Warranty void if set to No.
[Yes]
6. HMI and settings