4. Interfaces and Communication
Submenu Available settings Default settings
In/Out settings
Output voltage [200V] [208V] [220V] [230V] [240V] [230V]
Output frequency Mode: [Normal] [Converter] [Marine]
Frequency can be changed in Frequency
[Converter] mode
In [Marine] mode output frequency
follows input frequency
[Normal]
Output mode Mode: [Industrial] [IT] [Custom]
Overload: [Inv>Stop] [Inv>BP]
[Inv>BP>Inv]
Short-circuit: [Inv>Stop] [Inv>BP]
[Inv>BP>Inv]
[IT]
[Inv>BP>Inv]
[Inv>Stop]
Input volt hysteresis Sets input voltage hysteresis
from [1] to |10V]
[10V]
High Efficiency
mode
[Enabled] [Disabled]
Power the output from Bypass for high
efficiency
[Disabled]
Bypass settings
[Volt low]
[Volt high]
[Qualify]
[Hz synch]
[Unsynch]
[160V];
[276V];
[In spec];
[5%];
[Half cycle]
Load segments
[Auto start delay]
[Auto shutdown delay]
UPS: [0s]; Group1: [3s];
Group2: [6s]
UPS: [Disabled]; Group1:
[Disabled]; Group2:
[Disabled]
Overload
prealarm
[10%] … [102%]
Load % when overload alarm occurs
[102%]
On/Off settings
Start/Restart [Cold start] [Auto restart] [Auto start]
[Start on bypass]
[Cold start] [Auto restart] are
Enabled
[Auto start] [Start on bypass]
are Disabled
Forced reboot [Enabled] [Disabled]
[Timer] [10s] … [180s]
When mains recover during a shutdown
sequence:
If set to Enabled, shutdown sequence
will complete and wait 10 seconds prior
to restart,
If set to Disabled, shutdown sequence
will not complete, UPS stays on.
[Enabled]
[10s]
Energy saving [Enabled] [Disabled]
[Time] [1min] … [15min]
[Level] [100W] … [1000W]
If Enabled, UPS will shut-down after
defined duration. of back-up time, if
load is less than set value.
[Disabled]
[5min]
[100W]
Sleep mode [Enabled] [Disabled]
[Timer] [10min] … [120min]
If Disabled, LCD and communication
will turn OFF immediately after UPS
is OFF.
If Enabled, LCD and communication
stays ON 1h30 min after UPS is OFF.
[Enabled]
[90min]
Site wiring fault [Enabled] [Disabled]
Prevents from starting the UPS in case
of phase vs neutral wires swapping.
[Disabled]
Power Off alert [Enabled] [Disabled]
If Enabled, activates a confirmation
screen that requires user confirmation
after pressing the power button, before
the UPS shutdown occurs.
[Enabled]