Page 45
614-20306-00 - 9SX 0-6 KVA EMEA_EN
6. UPS maintenance
• Replacing the internal battery - TOWER 0-3KVA
The internal battery is heavy. Use caution when handling heavy batteries.
To replace the battery pack:
1. Unlock the lugs on the upper part of the front
panel.
2. Rotate the front face.
3. Remove the lower part of the front panel.
A ribbon cable connects the LCD control
panel to the UPS. Do not pull on the
cable or disconnect it.
4. Disconnect the internal battery connector.
5. Unscrew and remove the 2 screws of the metal
battery cover.
6. Pull up the metal battery protection cover.
7. Remove the battery cover to free the battery
pack.