Page 54
614-20306-00 - 9SX 0-6 KVA EMEA_EN
8. Specifications
Table 5. Electrical input connections
Part Number Input connection Input cable
9SX700I
IEC C14-10A NA (1)
9SX1000I
9SX1000IM
9SX1000IR
9SX1500I
9SX1500IR
9SX2000I
9SX2000IR
9SX3000I
IEC C20-16A Schuko 16A to IEC320/16A (2)
9SX3000IM
9SX3000IR
9SX5KI
Hardwired NA
9SX6KI
(1) If used in 2W + PE confi guration, customer should use input power cord IEC C13 to NEMA 6-15P or L6-15P.
(min18 AWG / 3C , min 300V, 105 °C ,min 1.5 m, max 4.5 m)
(2) If used in 2W + PE confi guration, customer should use input power cord IEC C19 to NEMA 6-20P or L6-20P.
(min14 AWG / 3C , min 300V, 105 °C , min 1.5 m, max 4.5 m)
Table 6. Electrical output
All models Normal mode High Efficiency mode Battery mode
Voltage regulation ±2% ±3%
Efficiency
700VA 87% 92% 79%
1KVA 88% 94% 82%
1.5KVA 91% 96% 82%
2KVA 92% 97% 84%
3KVA 92% 97% 84%
5KVA 94% 98% 92%
6KVA 94% 98% 92%
Frequency regulation Sync with line ±5% of nominal line frequency
(outside this range: ±0.5% of auto-selected nominal
frequency)
±0.5% of auto-selected
nominal frequency
Nominal output 200/208/220/230/240V for 0-3KVA (voltage configurable)
208/220/230/240V for 5-6KVA
Frequency 50 or 60Hz. autosensing or configurable as a frequency converter
0-3KVA 5-6KVA
Output overload
(Online mode)
102%~130%* 12 s 120 s
130%~150%* 2 s 30 s
>150%* Shutdown
immediately**
0.1 s**
Output overload
(Battery mode)
102%~130%* 12 seconds 120 s
130%~150%* 2 seconds 30 s
>150%* Shutdown
immediately**
0.1 s**
Output overload
(Bypass mode)
102%~110%* Overload warning
110%~130%* Shutdown after 5 mins
130%~150%* Shutdown after 15 s Shutdown after 15 s
>150%* Shutdown after 300 ms
Voltage waveform Sine wave
Harmonic distortion < 3% THDV on linear load
< 5% THDV on non-linear load
Power factor Up to 0.9
Load crest ratio Up to 3:1
* Percent is based on nominal Watt/VA
** Behaviour can change (see output mode in In/Out settings of the section 4.4)