Page 56
614-20306-00 - 9SX 0-6 KVA EMEA_EN
8. Specifications
Table 9. Battery
Internal batteries EBM
Tower configuration 700VA: 24Vdc - 2 x 12V. 9Ah
1000VA: 36Vdc - 3 x 12V. 9Ah
1500VA: 48Vdc - 4 x 12V. 9Ah
2000VA: 96Vdc - 8 x 12V. 7Ah
3000VA: 96Vdc - 8 x 12V. 9Ah
5KVA: 240Vdc - 20 x 12V. 7Ah
6KVA: 240Vdc - 20 x 12V. 7Ah
9SXEBM36T: 36Vdc - 2 x 3 x 12V. 9Ah
9SXEBM48T: 48Vdc - 2 x 4 x 12V. 9Ah
9SXEBM96T: 96Vdc - 2 x 8 x 12V. 9Ah
9SXEBM240T: 240Vdc - 2 x 20 x 12V. 7Ah
Rack configuration 1000VA: 36Vdc - 3 x 12V. 9Ah
1500VA: 48Vdc - 4 x 12V. 9Ah
2000VA: 72Vdc - 6 x 12V. 7Ah
3000VA: 72Vdc - 6 x 12V. 9Ah
9SXEBM36R: 36Vdc - 2 x 3 x 12V. 9Ah
9SXEBM48R: 48Vdc - 2 x 4 x 12V. 9Ah
9SXEBM72R: 72Vdc - 2 x 6 x 12V. 9Ah
Ty p e Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-year
float service life at 25 °C (77 °F)
Monitoring Advanced monitoring for earlier failure detection and warning
EBM battery cable
length
400 mm / 15.75 in