For more information visit: www.eaton.com IB01602008E
Instructional Booklet
Page 40 Effective: March 2014
ATC-300 Breaker Based Transfer Switch
Figure 41.ATC-300 Logic (Utility Supplying Load)
Step 6: To view the setpoints, press the <Step/Enter> pushbut-
ton and enter the Password.
Note: The factory default Password is 0300. Once all installation and test-
ing is complete, the Password should be changed by authorized per-
sonnel to a unique Password for the equipment.
After entering the password, press the <Step/Enter>
pushbutton until the VIEW SETPOINTS menu appears.
Select YES. Press the <Step/Enter> pushbutton to
scroll through the setpoints (Figures 42 through 43 and
Table 7).
Source 1
Source 2
Available
Available
Connected
Connected
Load
Unit Status
Alarm
Reset
Engine
Te st
Lamp
Te st
Help
Step
Enter
Bypass
TDNE / TDEN