Instructional Booklet
Page 44 Effective: March 2014
ATC-300 Breaker Based Transfer Switch
Table 7 Programmable Features and Setpoints (Cont.)
See tables in the appendix for Voltage and Frequency Pickup and Dropout settings.
SETPOINT SETPOINT UNITS DESCRIPTION RANGE FACTORY
DEFAULT
UNBAL PICK % Percent Percent for Unbalanced Voltage Pickup Dropout minus (UNBAL DROP % -2) to 3% 10%
UNBAL DELAY Seconds Unbalanced Delay Timer 10 to 30 0:20
TDEF Seconds Time Delay Emergency Fail Timer 0 sec to 6 sec 6
PHASE REV Phase Reversal OFF, ABC, or CBA OFF
DST ADJUST Day Light Savings 0 or 1 (1=Enabled) 1
LANGUAGE Selected Language English, French, or Spanish English
CHANGE TIME/DATE? Set Time and Date
Hours Set Hour 0 to 23 Eastern Standard
Time
MINUTES Set Minute 0 to 59 Eastern Standard
Time
WEEKDAY Set Weekday SUN, MON, TUE, WED, THU, FRI or SAT Eastern Standard
Time
MONTH Set Month JAN or 01 Eastern Standard
Time
DAY Set Day 1 to 31 Eastern Standard
Time
YEAR Set Year Current Year Eastern Standard
Time
RESET
SYSTEM COUNTERS?
Yes or No No
RESET ALL? Resets all System Counters Yes or No No
RESET
ENGINE RUN?
Hours Resets ENGINE RUN Counter 0 to 9999 XXXX
RESET
S1 CONN
Hours Resets S1 CONN Counter 0 to 9999 XXXX
RESET
S2 CONN
Hours Resets S2 CONN Counter 0 to 9999 XXXX
RESET
S1 AVAIL
Hours Resets S1 AVAIL Counter 0 to 9999 XXXX
RESET
S2 AVAIL
Hours Resets S2 AVAIL Counter 0 to 9999 XXXX
RESET
LOAD ENERG
Hours Resets LOAD ENERG Counter 0 to 9999 XXXX
RESET
TRANSFERS
Hours Resets TRANSFERS Counter 0 to 9999 XXXX
SAVE
SETPOINTS?
Save Changed Setpoints Yes or No Yes