EasyManua.ls Logo

Eaton ATC-300+ - Control Input Descriptions; Automatic Operation Mode; Manual Re-Transfer Procedure; Controller Operation

Eaton ATC-300+
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IM05805022K For more information visit: www.chfire.com
Instruction Booklet
Effective: January 2012 Page 15
ATC-300+ Automatic
Transfer Switch Controller
Section 5: Operation
5.1 General
This section specifically describes the operation and functional
use of the ATC-300+ Controller. The practical use of and opera-
tion within each category will be discussed. In this section, it is
assumed that prior sections of this manual were reviewed and
that the operator has a basic understanding of the hardware.
5.2 Automatic Mode
The Automatic Mode of the ATC-300+ Controller provides for
automatic transfer and re-transfer from Source to Source as dic-
tated by programmed setpoint values. It provides a summary of
the ATC-300+ Controller intelligence and supervisory circuits that
constantly monitor the condition of both the Source 1 and Source
2 power sources, thus providing the required intelligence for
transfer operations. These circuits, for example, automatically ini-
tiate an immediate transfer of power when the power fails or the
voltage level drops below a preset value. Exactly what the
ATC-300+ Controller will initiate in response to a given system
condition depends upon the combination of standard and selected
optional features.
5.3 Monitor Mode
Monitor Mode is a special operating mode in which the ATC-
300+ Controller does not provide control for transfer operations.
The ATC-300+ will, however, continuously monitor both Source
1 and Source 2 voltages and frequencies.
The ATC-300+ will be in Monitor Mode when the “Monitor
Mode” control input is in the “Connected” state as described in
Section 5.4. While in the Monitor Mode of operation, the ATC-
300+ LCD Display will display “ATS NOT IN AUTOMATIC”.
5.4 Control Inputs
The ATC-300+ has five individual input control signals. The
inputs are DC wetted with the unregulated DC supply and appro-
priate current limiting to provide a nominal current of 10 mA per
channel.
5.4.1 Control Input Descriptions
The Control Input “State” definitions are as follows.
Connected - When the input is shorted by an external contact or
connection.
Unconnected - When the input is NOT shorted by an external con-
tact or connection.
The Control Input operations are defined as follows.
Source 1 Closed
When this input is in the “Connected” state, it indicates to the
ATC-300+ Controller that the Source 1 device is closed. When
this input is in the “Unconnected” state, it indicates to the ATC-
300+ that the Source 1 device is open. This input is typically
wired to the Source 1 device auxiliary contact that is closed when
the Source 1 device is closed. The “Source 1 Closed” input is
always enabled.
Source 2 Closed
When this input is in the “Connected” state, it indicates to the
ATC-300+ Controller that the Source 2 device is closed. When
this input is in the “Unconnected” state, it indicates to the ATC-
300+ that the Source 2 device is open. This input is typically
wired to the Source 2 device auxiliary contact that is closed when
the Source 2 device is closed. The Source 2 input is always
enabled.
Lockout
When the “Lockout” input is in the “Unconnected” state, the ATC-
300+ Controller will not permit an automatic transfer operation.
When the “Lockout” input is in the “Unconnected” state, the LCD
Display will be active continuously. It will read “Lockout” on Line
2 of the LCD Display screen immediately, regardless of any con-
troller or switching device operation. When the “Lockout” input is
in the “Connected” state and the Alarm is reset, the ATC-300+
will permit automatic transfer operation. This input is typically
wired to the normally closed Source 1 and Source 2 device alarm
contact that opens when one of the devices has tripped due to a
fault current. The “Lockout” input is selectable as enabled or dis-
abled via factory control only.
Go To Source 2
When the “Go to Source 2” input is in the “Connected” state, the
ATC-300+ Controller is be in a normal, automatic operation
mode. When the “Go To Source 2” input is in the “Unconnected”
state, the ATC-300+ controller will initiate a generator start and
then transfer to the Source 2 power source. The ATC-300+ will
maintain the connection to Source 2 until the input changes to
the “Connected” state, upon which it will initiate a re-transfer to
the Source 1 power source. When the “Go To Source 2” input is
in the “Unconnected” state, the LCD Display will be active contin-
uously. Active time delays will be constantly displayed on Line 1,
with real-time remaining countdown to zero status. It will con-
stantly read “Go To Source 2” on Line 2 of the LCD Display. This
operation is “failsafe”. The “Go To Source 2” input is always
enabled. The “Go To Source 2” input does not have a user acces-
sible programmable setpoint for enable or disable.
Monitor Mode
When the “Monitor Mode” input is in the “Unconnected” state,
operation of the ATC-300+ Controller will not be effected. When
the “Monitor Mode” input is in the “Connected” state, the ATC-
300+ will monitor the Source 1 and Source 2 voltages and fre-
quencies but will not provide any control capabilities. When the
“Monitor Mode” input is in the “Connected” state, the ATC-300+
LCD Display will be active continuously and will constantly read
“ATS” on Line 1 and “NOT IN AUTOMATIC” on Line 2 of the LCD
Display. The “Monitor Mode” input does not have a user accessi-
ble programmable setpoint for enable or disable. This is NOT a
“failsafe” operation.
Manual Re-Transfer
With manual operation set, momentary closure on Pins 5 and 6 of
Connector J8 allows ATC-300+ to proceed with a re-transfer
operation at the operators discretion. Should a failure of the emer-
gency source occur while waiting for the manual return, the re-
transfer proceeds automatically.

Other manuals for Eaton ATC-300+

Related product manuals