EATON BiWire Flexi Installation Manual (PR215-216-520-03 15-03-16, PINSTFLEXIINST) March 2016 www.eaton.com 10
2.7 Status Indications
KEY
ON (---------) Indicator lit
OFF Indicator unlit
SLOW ( - - - - ) Indicator slow flashing, buzzer slow pulsing
FAST ( - - - - - ) Indicator fast flashing, buzzer fast pulsing
SILENT Sounders off, buzzer off
CONT Sounders on, buzzers continuous
Any condition could be indicated
Figure 6: Visual Indications
The BiWire Flexi Fire Detection & Alarm System
Normal Condition ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF Normal condition and at access level 1
Access Level 2 ON FAST Access level 2 pass code accepted
Fire Condition ON ON ON ON CONT CONT Only the zone in fire will have its zone fire indicator lit
System Fault ON ON ON SLOW Severe fault condition with the panel
Repeater Fault ON ON SLOW SLOW There is a problem with the link between panel and
repeater
Battery Fault ON ON SLOW SLOW No battery voltage or battery voltage too low
Mains Fault ON ON ON SLOW Mains voltage has been lost
Battery Failure ON ON SLOW SLOW Battery impedance fault
Charger Fault ON ON ON SLOW Charger voltage fault
Sounder Fault ON ON SLOW SLOW Short or Open circuit condition on the sounder circuit
FRE Fault ON ON SLOW SLOW Short or Open circuit condition on the FRE
FPE Fault ON ON SLOW SLOW Short or Open circuit condition on the FPE
Zone Fault ON ON SLOW SLOW Short or Open circuit condition or head removal on
the zone
Detector Removed ON ON FAST SLOW BiWire Zones Only can detect when a Detector head
has been removed
Sounder Disabled ON ON ON ALL fire alarm devices on ALL zones disabled
FRE Disabled ON ON ON FRE disabled
FPE Disabled ON ON ON FPE disabled
Zone Disabled ON ON ON Zone is disabled from fire detection
Individual Zone Test Active ON ON ON SLOW An individual zone is in test mode and awaiting a fire
activation
Power ON
General Fault
General Disable
Repeater Fault /
System fault
Battery Fault /
Mains Fault
Battery Failure /
Charger Fault
Sounder Fault /
Sounder Disabled
Self Test On \ Test
FRE On
FRE Fault /
FRE Disabled
FPE Fault \
FPE Disabled
General Fire
Zone Fire (1-8)
Detector Removed \ Zone
Fault \ Zone Disabled
Fire Alarm Devices
Panel Buzzer
Comments
Condition
Visual Indications
Audiable
Indications