EasyManua.ls Logo

Eaton BiWire Flexi - Option Board for FRE, FPE, and Zonal Relays

Eaton BiWire Flexi
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EATON BiWire Flexi Installation Manual (PR215-216-520-03 15-03-16, PINSTFLEXIINST) March 2016 www.eaton.com 11
Auxiliary Output
The Auxiliary Output is a 30V DC output provided at the
panel to power ancillary equipment. The current consumed
by this output must be considered when calculating battery
standby times. The contacts are not monitored.
Class Change
The sounders can be operated by an external volt free
contact. A short circuit at this terminal will activate non-
latching sounders (no indication will show on the fire alarm
panel). The sounders will automatically silence when the
short circuit is removed. This is sometimes used for schools
at class change times.
NO VOLTAGE SHOULD BE APPLIED TO THIS INPUT
2.8 Control Panel Inputs and Outputs
Figure 7: Panel Wiring Diagram
Figure 8: Auxiliary Output Terminal
Figure 9: Class Change Input Terminal
WARNING
The BiWire Flexi Fire Detection & Alarm System
www.acornfiresecurity.com
www.acornfiresecurity.com

Table of Contents

Other manuals for Eaton BiWire Flexi

Related product manuals