EATON BiWire Flexi Installation Manual (PR215-216-520-03 15-03-16, PINSTFLEXIINST) March 2016 www.eaton.com 18
Connecting the Zone Cables
Connect the cables (clearly labelled with the zone numbers)
to the appropriate zone +/- terminals, observing the correct
polarity (see Figure 21).
If any of the zones are not used then the EOLM-3 must
remain fitted to the terminals of that zone to ensure the
system remains fault free.
Installation Instructions
NOTE
Figure 22: Panel Wiring Diagram
Battery Connections
Figure 21: Battery Connection
CAUTION
IT IS IMPORTANT THAT ZONE CABLING IS CONNECTED
TO THE CORRECT ZONE INPUT OTHERWISE ANY FIRE
OR FAULT INDICATION ON THE PANEL WILL NOT
MATCH THE ZONE MAP OF THE SITE, AND WILL NOT BE
COMPLIANT TO BS5839.
Battery Connections:-
1. Connect the BLACK battery wire to the BLACK (-) battery
terminal of battery B
2. Connect the RED battery wire to the RED (+) battery
terminal of battery A
3. Connect the link cable between the two remaining
terminals
ZonesSounders
DO NOT USE A HIGH VOLTAGE INSULATION TESTER
www.acornfiresecurity.com